Monday, December 23, 2013

what is epm in boilers, condensers, evaporators, feed water tanks


epm meaning = equivalents per million

- a water analysis reporting method in which the results are on an ion basis
- an ion is an atom or molecule with a net electric charge because of gaining or losing electron(s).
- chemical components of analysis are based on a common denominator which is the chemical equivalent weight
- not a commonly accepted standard, not recommended for use in plants
- advantage of this approach is mainly for simplicity of calculation


ppm meaning = parts per million

1 ppm = 0.0001% which is one ten-thousandth of one percent
one part (by weight) per million parts (by weight)
example: 1 kg of salt is dissolved in 1,000,000 kg of water [ 1 ppm salt in water ]
simpler, reliable, commonly accepted standard for water analyses reports
for feed water analysis in boilers, condensers, evaporators, and other steam plant equipment

Friday, December 20, 2013

What is back pressure in centrifugal pump


Back pressure in centrifugal pump

- area of volute casing is greater at discharge than at suction side
- velocity of fluid at the discharge is lesser than at the suction side
- pressure at discharge side is greater than at the suction side
- volume of fluid at discharge is larger than at the suction side


Analysis of Volute Casing of the Centrifugal Pump:


Similar to the Venturi principle & Bernoulli's principle,

SUCTION SIDE

- smaller area
- greater fluid velocity
- lesser pressure
- smaller fluid volume

DISCHARGE SIDE

- larger area
- lesser fluid velocity
- greater pressure
- larger fluid volume

Important:

1.  At the discharge side of the pump, there is more space for the fluid, thereby causing the fluid to slow down in speed and lose kinetic energy.

2.  First Law of Thermodynamics states that energy is neither created nor destroyed but is transformed or converted to another form.

3.  The fluid at the pump discharge decreased in kinetic energy (speed is reduced) but the reduction in kinetic energy is converted into pressure energy, therefore, the discharge pressure is higher than the suction pressure.


Back pressure of a valve at the discharge side of centrifugal pump:

- back pressure is the pressure behind the flow (at the back of the flow)
- backpressure is the pressure at the inlet side of the discharge valve (which is mounted at the discharge side of the pump)
- backpressure is created by restricting the flow (closing the valve that is mounted at the pump discharge)


Analysis of Valve Fitted at Discharge side of Centrifugal Pump:

When the valve is restricted (slightly closed down),

VALVE INLET

- higher back pressure
- higher volume
- slower fluid speed

VALVE OUTLET

- lower pressure
- lower volume
- faster fluid speed


Benefit of back pressure in centrifugal pumps:

- higher back pressure at the inlet of the discharge valve will decrease the power requirement of the driving motor of the pump


Effects of higher back pressure in centrifugal pumps:

- flow at the discharge valve outlet is reduced
- pressure of fluid at the discharge valve outlet is reduced
- longer time to fill up (tank, container, etc.)
- longer time to empty (tank, container, etc.)


Reasons Why are Centrifugal Pumps widely used in the industries?

- large flowrates handling capacity
- versatile
- simple in construction
- cheaper price
- easier and less expensive to operate, maintain and repair


How does regenerative condenser work


Purpose of regenerative condenser

- to increase thermal efficiency by using some of the steam in the shell of the condenser to reheat the falling condensate to be used for boiler feed water

How does regenerative condenser work:

- baffle plates in a shell and tube condenser are arranged in a configuration which allows most of the steam that enters the shell of the condenser to come in contact with the cooling tubes containing the cooling medium

- majority of the steam then condenses and fall to the condenser hot well

- a portion of the steam, however, is distributed by means of the design of the baffle plates so that it will direct this portion of steam to bypass the cooling tubes and flow directly to the bottom of the shell in order to reheat the falling condensate (the condensate which was the "most of the steam", that is now condensed by means of the cooling medium in the tubes)

- this process will make the temperature of the condensate from the hot well to approach the saturation temperature at condenser pressure

- when the condensate is near the saturation point, the unwanted corrosive non-condensable gases such as oxygen and carbon dioxide will escape

 

Sunday, December 1, 2013

Purpose of Staging in Turbines


Why turbines have stages?

What is a steam turbine stage?

- a stage is a pair of rotating and stationary blades (diaphragm, nozzle)
- the rotating blades are attached to the rotor
- the stationary blades (stators) are attached to the turbine casing
- steam pressure and temperature drops as it expands and passes to the stages
- steam expansion means increase in volume meaning larger surface area


Why do steam turbines have multiple stages? Why not just use a single stage turbine?

- one stage extracts only a small portion of the available energy from the steam
- more stages means more energy extracted
- more energy means more mechanical work at the shaft
- more work means more power (shaft horsepower)



Why turbines need higher vacuum (lower pressure)?

- higher condenser vacuum pressure (lower pressure) means lower exhaust temperature of the steam
- higher vacuum pressure means higher thermal efficiency
- higher efficiency means higher power output
- higher efficiency means lesser power losses


Pressure is inversely proportional to Area


HIGH PRESSURE (HP) TURBINE
- steam is at Higher pressure
- steam is at Higher temperature
- steam is at Higher speed
- turbine has Lesser area (lesser diameter)

LOW PRESSURE (LP) TURBINE

- steam is at Lower pressure
- steam is at Lower temperature
- steam is at Lower speed
- turbine has Larger area (larger diameter)

Monday, September 23, 2013

Pumps in Parallel, Pumps in Series Connection

Two Pumps Connected in Parallel


- purpose: to pump fluid in higher capacities, higher volume, higher amount

- head is constant (total dynamic head is the same, uniform)

- higher discharge volumes

- increase in total pumping capacity

- add flowrates of pumps


Total Flow = Flowrate of Pump1 + Flowrate of Pump2

Q = q1 + q2


Two Pumps Connected in Series


- purpose: to pump fluid in higher elevation, higher height, higher level

- fluid flowrate is constant (the same, uniform)

- higher discharge heights

- increase in total dynamic head

- add heads of pumps 


Total Dynamic Head = Head of Pump1 + Head of Pump2

TDH = H1 + H2

Wednesday, July 17, 2013

Air Conditioning Heat Load Calculation (Room & Building estimate)


The calculation estimate formulas used here are just rough approximations to simplify the total heat load calculations and quickly select an air conditioning unit capable of providing the necessary cooling of the room or space.


--------------------- QUICK HEAT LOAD CALCULATION ESTIMATE -------------------

Typical Room or Small Office:


Space Heat Load = Cooling Space Dimensions x 4

Space Heat Load = Room Length (ft) x Room Width (ft) x Room Height (ft) x 4

Space Heat Load = L x W x H x 4


Occupant Load = 600 BTU/person


Total Heat Load = Space Heat Load + Occupant Load




------------------- DETAILED HEAT LOAD CALCULATION ESTIMATE ------------------
     
1 Btu (British thermal unit)
1 Btu = energy required to cool or heat 1 pound of water by 1 degree Fahrenheit

Heat Load of People
Heat generated per person = 600 Btu

Units:

1 Btu = 0.3 watt hours
1 Btu = 250 calories
1 Btu = 0.25 kilocalories

1 watt-hour = 3.4 BTU

1 TON of cooling = 12,000 BTU/hour

1 TON of refrigeration = 12000 Btu/hr
1 TON of refrigeration = 200 Btu/min
1 TON of refrigeration = 3.5 KJ/s
1 TON of refrigeration = 3.5 KW  



Total Heat Load:

The total heat load of a room/building is a function of:
1. Size of space to be cooled
2. Area of windows
3. Number of occupants
4. Equipment heat load
5. Lighting heat load

Total Heat Load
= Space Btu + Window Btu + Occupant Btu + Equipment Btu + Lighting Btu

 

   
Example:
Calculate the Total Heat Load and select an Air Conditioning Unit.

Room dimensions:
Length, L = 15 ft
Width, W = 10 ft
Height, H = 8 ft (2.5 m height from floor to ceiling)

Window dimensions:
L = 4 ft
W = 4 ft

Occupants:
2 persons

Equipment wattage:
TV = 100 watts
Radio = 50 watts
Laptop = 60 watts

Lighting Load:
60 watts light bulb


Air-conditioning Heat Load Estimation Formulas:


Total Heat Load
= Space Btu + Window Btu + Occupant Btu + Equipment Btu + Lighting Btu

Space Btu = Room Length (ft) x Room Width (ft) x 32

Window Btu = Total Window Area (sq. ft) x 80

Occupant Btu = Number of Occupants x 600

Equipment Btu = Total Equipment Wattage x 3.4

Lighting Btu = Total Lighting Wattage x 4.3


Total Heat Load Calculation:


Space Btu:
Space Btu = Room Length (ft) x Room Width (ft) x 32
Space Btu = L x W x 32
Space Btu = 15 x 10 x 32
Space Btu = 4800 Btu

Window Btu:
Window Btu = Total Window Area (sq. ft) x 80
Window Btu = Window Length (ft) x Window Width (ft) x 80
Window Btu = L x W x 80
Window Btu = 4 x 4 x 80
Window Btu = 1280 Btu

Occupant Btu:
Occupant Btu = Number of Occupants x 600
Occupant Btu = 2 persons x 600
Occupant Btu = 2 x 600
Occupant Btu = 1200 Btu

Equipment Btu:
Equipment Btu = Total Equipment Wattage x 3.4
Equipment Btu = (TV watts + Radio watts + Laptop watts) x 3.4
Equipment Btu = (100 watts + 50 watts + 60 watts) x 3.4
Equipment Btu = (100 + 50 + 60)  x 3.4
Equipment Btu = 714 Btu

Lighting Btu:
Lighting Btu = Total Lighting Wattage x 4.3
Lighting Btu = 60 watts x 4.3
Lighting Btu = 60 x 4.3
Lighting Btu = 258 Btu


Total Heat Load
= Space Btu + Window Btu + Occupant Btu + Equipment Btu + Lighting Btu
= 4800 + 1280 + 1200 + 714 + 258
= 8252 Btu

Select 8000 Btu to 10,000 Btu Air Conditioning Unit


Commercial Air Conditioner Unit Selection & Prices (July 2013):

5000 Btu Room Air Conditioner

150 sq. ft. bedroom (15 ft x 10 ft) or 15 sq. meter (5 m x 3 m)
Price: $100


8000 Btu Room Air Conditioner

300 sq. ft. master bedroom (20 ft x 15 ft) or 35 sq. meter (7 m x 5 m)
Price: $200


10,000 Btu Room Air Conditioner

450 sq. ft. living room (30 ft x 15 ft) or 50 sq. meter (10 m x 5 m)
Price: $400


See also:
1. Basics of Refrigeration and Air Conditioning
*.
*.
*.
*.
*.
*.



#RX#

Sunday, July 14, 2013

Why motors have large starting current

Reasons why motors have big starting current or inrush current:

- running motors produce back emf (electromotive force) in their coils

- back emf is caused by magnetic field which resists current (flow of electrons) through the armature winding

- back emf functions like a resistor which prevents current flow

- no back emf exists when motor is not running

- no back emf when motor is at rest

- at start up, resistance is zero (which is a short circuit condition), therefore current is large because no resistance to flow of current

- when a motor is running, the armature windings produce a resisting voltage (pressure) which opposes current flow as long as it is running

- a motor at rest acts like a transformer having secondary winding short circuited because the rotor windings in a squirrel cage induction motor is short circuited (closed circuit)

- starting currents (in-rush currents) for induction motors generally are 8 to 10 times the rated full load current

- a motor at rest has large inertia, therefore larger current is required to start it (this is similar to pushing a cart from stationary position, it's harder to push at the beginning, you need to exert a larger force and power, but as soon as the wheels start rolling, it is easier to push the car once it is moving)