Shop at Amazon.ca

Saturday, October 29, 2022

REFRIGERATION HVAC MECHANIC RED SEAL LICENSE EXAM REVIEWER - capacitance of parallel capacitors

Watch this video in my YouTube channel 

Eternalson17

YouTube link


REFRIGERATION HVAC MECHANIC RED SEAL LICENSE EXAM REVIEWER - capacitance of parallel capacitors 


PROBLEM:


Two capacitors having 50 uF and 150 uF respectively are wired in parallel. What is the value of the total capacitance?


Given 

capacitance1 = 50 uF


capacitance2 = 150 uF



Unknown 

Total capacitance of circuit 



SOLUTION:


Parallel Capacitors: additive


Total Capacitance, Ct = C1 + C2


Ct = 50 + 150


Ct = 200 uF


Note:

If these same two capacitors were wired in series, the total capacitance would be 37.5 uF, reduced to almost 20%.



*

REFRIGERATION HVAC MECHANIC RED SEAL LICENSE EXAM REVIEWER - cooler/reefer tonnage capacity

Watch this video in my YouTube channel 

Eternalson17

YouTube link


REFRIGERATION HVAC MECHANIC RED SEAL LICENSE EXAM REVIEWER - cooler/reefer  tonnage capacity 



PROBLEM:


An 8 x 20 ft sea container reefer walkin cooler has an hourly load of 22,500 Btu/hr and operates 24 hours a day. The defrost system runs for 15 minutes every hour. Calculate the tonnage capacity in Tons of Refrigeration and in Kilowatts.


Given

22,500 Btu/hr hourly load

24 hours operation 

15 minutes defrost per hour


Unknown 

Reefer capacity in tons and KW



SOLUTION:


Total defrost time

= 15 minutes x 24

= 360 minutes

= 6 hours


Total Run-Time

= 24 - 6

= 18 hours


Q = hourly load 

       x 24/run time 


Walk in Cooler Condensing Unit capacity

= ( Hourly Load x 24 hr ) / 18 hr Run-Time

= ( 22,500 x 24 ) / 18

= 30,000 Btu/hr


Tonnage capacity = 30,000/12,000 = 2.5 tons


Capacity in Kilowatts = 2.5 x 3.5 = 8.8 KW



*

REFRIGERATION HVAC MECHANIC RED SEAL LICENSE EXAM REVIEWER - water flow rate of chiller

Watch this video in my YouTube channel 

Eternalson17

YouTube link


REFRIGERATION HVAC MECHANIC RED SEAL LICENSE EXAM REVIEWER - water flow rate of chiller


PROBLEM:

A chiller has a capacity of 75 tons with a heat rejection ratio (HRR) of 1.3. If the change in temperature is 10F, solve for the water flow rate in US gallons per minute and imperial gallons per minute.


Given

chiller capacity = 75 tons

heat rejection ratio = 1.3

delta T = 10F


Unknown

US gpm

imperial gpm


SOLUTION:


Converting tons to Btu/hr 

Q = 75 tons x 12,000 Btu/hr per ton = 900,000 Btu/hr


Incorporating the HRR and rearranging the main equation,


US gpm = Q x HRR/(500 x delta T)


US gpm = 900,000 x 1.3/(500 x 10)


US gpm = 234 US gallons


To solve for imperial gallons, change the constant to 600


imperial gpm = Q x HRR/(600 x delta T)


imperial gpm = 900,000 x 1.3/(600 x 10)


imperial gpm = 195 imperial gpm




*

REFRIGERATION HVAC MECHANIC RED SEAL LICENSE EXAM REVIEWER - water temperature entering chiller

Watch this video in my YouTube channel 

Eternalson17

YouTube Link


REFRIGERATION HVAC MECHANIC RED SEAL LICENSE EXAM REVIEWER - water temperature entering chiller


PROBLEM:


A 60 ton chiller circulates 160 US gallons of water. What is the temperature rise? If the water supply temperature is 45F, determine the temperature of the water entering the chiller.


Given

Cooling capacity = 60 tons 

gpm = 160 US gallons

suppy temperature = 45F


Unknown

Temperature rise = ? or change in temperature (delta T)

Temperature of water entering chiller = ? or return temperature


SOLUTION:


Converting tons to Btu/hr 

Q = 60 tons x 12,000 Btu/hr per ton = 720,000 Btu/hr


Rearranging the main equation Q = 500 x gpm x delta T 


delta T = Q/(500 x gpm)


delta T = 720,000/(500 x 160)


delta T = 9 F


return temperature = delta T + supply temperature


return temperature = 9 + 45


return temperature = 54 F



*






REFRIGERATION HVAC MECHANIC RED SEAL LICENSE EXAM REVIEWER - chiller cooling capacity (tonnage)

 

Watch this video in my YouTube channel

 Eternalson17

YouTube Link 


REFRIGERATION HVAC MECHANIC RED SEAL LICENSE EXAM REVIEWER - chiller cooling capacity (tonnage) PROBLEM: Calculate the tonnage of a water chiller having a water flow rate of 240 US gallons with a supply temperature of 45F and a return temperature of 55F.

Given gpm = 240 US gallons supply temperature = 45F return temperature = 55F Unknown Q = ? cooling capacity in tons of refrigeration

SOLUTION: Q = 500 × gpm x delta T Q = 500 × 240 x (55 - 45) Q = 500 × 240 x 10 Q = 1,200,000 Btu/hr

The conversion is 1 Ton = 12,000 Btu/hr, so the final answer is, Tonnage = 1,200,000/12,000 Tonnage = 100 tons *







REFRIGERATION HVAC MECHANIC RED SEAL LICENSE EXAM REVIEWER - walk in freezer hourly load

Watch this video in my YouTube channel Eternalson17:

 YouTube Link 


REFRIGERATION HVAC MECHANIC RED SEAL LICENSE EXAM REVIEWER - walk in freezer hourly load


PROBLEM:


A 3 ton walkin freezer operates 24 hours a day and the defrosting system runs for 10 minutes every hour. Determine the hourly load in Btu/hr.


SOLUTION:


Total defrost time

= 10 minutes x 24

= 240 minutes

= 4 hours


Total Run-Time

= 24 - 4

= 20 hours


Walk in Freezer Condensing Unit capacity

= ( Hourly Load x 24 hr ) / 20 hr Run-Time


3 x 12,000 = Hourly Load x 24/20


Hourly Load = 36,000/1.2


Hourly Load = 30,000 Btu/hr



*


Tuesday, December 19, 2017

Walk-in cooler wiring diagram, walk in freezer, domestic refrigerator wiring

                                         
                                           Walk-in cooler mechanical diagram:



                               Walk-in freezer electrical wiring diagram with heater



                             Walk in freezer with defrost - electrical wiring diagram




                         Walk-in cooler with pump down - electrical wiring diagram



 
                          Walk in freezer with electric defrost - electrical wiring diagram





                              Domestic refrigerator - simple electrical wiring diagram

Watch Youtube video: