REFRIGERATION
TROUBLESHOOTING FLOWCHART
There are
7 Steps of a Systematic Refrigeration Troubleshooting Flowchart.
1. Determine Problem
2. Look for Signs/Symptoms
3. Determine Causes of Problem
4. Perform Logical Elimination Process
5. Find the Most Probable Cause
6. Correct the Defect
7. Recheck System Operation
MOST
COMMON REFRIGERATION PROBLEMS
1.
Undercharge/Leak
2.
Frozen/Iced Evaporator
3.
Overcharge
4.
Restriction
5. High
Discharge Temperature/High Head Pressure
6.
Compressor Problems
7.
Fan/Motor Problems
8.
Electrical Components Problems
Example I:
REFRIGERATION TROUBLESHOOTING FLOWCHART
1.
Determine Problem: POOR COOLING
2.
Signs/Symptoms:
·
presence
of oil leaks
·
rapid
compressor cycling (orifice tube systems)
·
bubbles/foam
on sight glass
·
low
side/suction pressure Low
·
high
side/discharge/head pressure Low
3.
Possible Causes of Problem:
·
undercharged
– insufficient refrigerant charge (foam/bubbles in sight glass)
·
leak
·
plugged
suction filter
·
ice
build up on evaporator
·
dirty
evaporator
·
restriction
in evaporator
·
faulty/defective
fan
·
metering
device (expansion valve) underfeeding
4.
Perform Logical Elimination Process
- narrow down the causes of the problem in
logical systematic fashion
5. Find
Most Probable Cause
- using tools to conduct functional tests
and performance tests to find out
the most likely root cause of the
problem
- example: most probable cause is
undercharge due to a leak
6.
Correct the Defect
- repair the leak and add appropriate
amount of refrigerant
7.
Recheck System Operation
- conduct another performance test and
check temperatures and pressures
to ensure system is back to correct
normal operation
Example
2: NO COOLING – UNDERCHARGED/LOW
REFRIGERANT/LEAK
Actual
Repairman/Serviceman procedure: R22 system
1.
Customer complaint report – NO COOLING
2. Look
at the Thermostat, ensure it is in COOL mode and set at 70 F
3. Feel
the supply duct whether it is blowing hot air
4. Check
the return air filter
5.
Determine which loads are running: Indoor Fan, Outdoor Fan, Compressor
6.
Measure amperage of compressor using Multi-tester clamp-on meter (for
Residential AC: normal compressor amps = 11 A)
7. By the
process of elimination, since all 3 loads are running, therefore the problem is
mechanical
8. Check
for debris around condensing unit (leaves, grass, etc.)
9.
Calculate Superheat:
a. Measure indoor wet bulb temperature – place
psychrometer in return air duct (psychrometer reading: 70 F)
b. Measure outdoor dry bulb temperature – place
psychrometer near condensing unit (measurement reading: 95 F)
c. Measure suction line pressure using
manifold gage (reading: 50 psig)
d. Use PT CHART to determine evaporation
temperature corresponding to 50 psig --- 26 F
e. Determine actual temperature of suction
line using Multimeter Probe: 75 F
f. Calculate
Superheat = Actual suction line temp – evaporation temp at 50 psig
Superheat = 75 – 26 = 49 F
g. Using SUPERHEAT CHART corresponding to
95 F dry bulb and 70 F wet bulb temperatures, the superheat is 18 F
10. Using
Mechanical Air Conditioning Fault Table, determine what the problem is:
Leak/Undercharged
11. Check
for leaks on the indoor & outdoor units using soap and bubble or electronic
leak detector
12. Add
refrigerant
---------------------------------------------------------------------------------------------------
Determine
Problem: INADEQUATE COOLING
Signs/Symptoms:
- suction
pressure is high
- head
pressure is high
-
continuous compressor operation (orifice tube systems)
- ice or
frost on condenser
- ice on
evaporator coil
Possible
Causes:
-
overcharged – too much refrigerant charge
-
evaporator freeze up/iced up
-
thermostat temperature setting too high
- dirty
condenser coil
-
restriction in condenser coil
- fan not
running
- fan
blade reversed
- poor
air circulation
-
excessive load/warm products
- door
open/door seal broken
-
thermostatic expansion valve (TXV/TEV) overfeeding
-
insufficient clearance around cabinet
- high
ambient temperature
Determine
Problem: RESTRICTION
Signs/Symptoms:
- no
cooling/poor cooling
- gauge
pressures lower than normal
-
compressor cycles frequently
- frost
on high pressure lines
- suction
pressure is from low to vacuum
- head
pressure is low
Possible
Causes:
-
defective compressor
-
contaminants such as dirt or corrosion
-
defective TXV/TEV
- plugged
orifice
-
plugged/defective filter-drier
------------ OTHER
REFRIGERATION PROBLEMS ------------
Compressor Not Running,
Correct Voltage & Phase:
1. Check voltage within 10%
2. Check Overload Protector
3. Check Start Capacitor
4. Check Start Relay
5. Check Amp Draw of compressor. If very low compared to RLA/FLA, check:
_ broken discharge valves
_ broken suction valves
_ broken crank
_ broken push rod
Compressor Not Running, Incorrect Voltage & Phase:
1. Test circuit for voltage loss & phase loss
2. Test contactor
3. Check control relay
4. Check safety devices such as High Pressure Switch, Low Pressure Switch, Oil Pressure Safety Switch.
5. Before pressing Reset on the safety devices, find out reason why it tripped and fix it.
High Head Pressure on Water-cooled Condenser:
1. Check High Pressure Control. If tripped, adjust setting on water regulating valve to achieve manufacturer's recommended pressure.
2. Check water flow. If insufficient:
- check water supply and plumbing
- check water inlet temperature
- check water outlet temperature, if high, adjust water regulating valve to recommended pressure
- check condition of valve, if defective, worn or scaled with calcium/mineral deposit, replace valve
3. If water flow is sufficient:
- reset high pressure control if tripped
- determine temperature differential (TD) between condenser water outlet & inlet
- if TD is too low, condenser is dirty or has calcium/mineral build-up
- acid solution can be circulated into condenser to remove mineral deposits and improve heat transfer according to manufacturer's instructions/procedure
High Head Pressure on Air-cooled Condenser:
1. Check if condenser is dirty, clean coil using wash down or high pressure system
2. Check condenser fan motor correct rotation
3. Check for worn, loose or broken belt
4. Check fan blade condition, size, and correct direction (not installed backwards)
5. Check motor bearing, if there is side to side play, replace motor
6. If condenser is facing south, move north or install shade
7. If ambient temperature is high or condenser is located near heat-producing equipment, relocate and find solution to prevent overheating
1. Check voltage within 10%
2. Check Overload Protector
3. Check Start Capacitor
4. Check Start Relay
5. Check Amp Draw of compressor. If very low compared to RLA/FLA, check:
_ broken discharge valves
_ broken suction valves
_ broken crank
_ broken push rod
Compressor Not Running, Incorrect Voltage & Phase:
1. Test circuit for voltage loss & phase loss
2. Test contactor
3. Check control relay
4. Check safety devices such as High Pressure Switch, Low Pressure Switch, Oil Pressure Safety Switch.
5. Before pressing Reset on the safety devices, find out reason why it tripped and fix it.
High Head Pressure on Water-cooled Condenser:
1. Check High Pressure Control. If tripped, adjust setting on water regulating valve to achieve manufacturer's recommended pressure.
2. Check water flow. If insufficient:
- check water supply and plumbing
- check water inlet temperature
- check water outlet temperature, if high, adjust water regulating valve to recommended pressure
- check condition of valve, if defective, worn or scaled with calcium/mineral deposit, replace valve
3. If water flow is sufficient:
- reset high pressure control if tripped
- determine temperature differential (TD) between condenser water outlet & inlet
- if TD is too low, condenser is dirty or has calcium/mineral build-up
- acid solution can be circulated into condenser to remove mineral deposits and improve heat transfer according to manufacturer's instructions/procedure
High Head Pressure on Air-cooled Condenser:
1. Check if condenser is dirty, clean coil using wash down or high pressure system
2. Check condenser fan motor correct rotation
3. Check for worn, loose or broken belt
4. Check fan blade condition, size, and correct direction (not installed backwards)
5. Check motor bearing, if there is side to side play, replace motor
6. If condenser is facing south, move north or install shade
7. If ambient temperature is high or condenser is located near heat-producing equipment, relocate and find solution to prevent overheating
--------------------------------------------------------------------------------------
NORMAL
CONDITIONS FOR R134A SYSTEM:
Ambient temp: 80 F --- 27 C
Humidity: 50% RH
Air
outlet temp of supply: 12 C --- 53 F
Lo-Side: 40 psig
Hi-Side: 320 psig
Sight
glass: clear --- adequate refrigerant
(foamy --- insufficient
refrigerant
frosty --- almost
nothing
no foam --- too much)
Air
Conditioning Diagnostic Charging Table:
Compressor and Electric Components
Troubleshooting:
Refrigeration Troubleshooting: Causes and
Remedy
AC/Furnace Troubleshooting:
Heat Pump Troubleshooting Guide:
Sample Refrigeration Troubleshooting
Flowchart:
Table 1. HOW TO TROUBLESHOOT COMMON REFRIGERATION PROBLEMS:
PROBLEM
|
POSSIBLE CAUSES
|
SOLUTION/REMEDY
|
System Not Running
|
Power cord not plugged in
|
Plug in power cord
|
Fuse blown
|
Replace fuse; find out reason
blown
|
|
Circuit breaker tripped
|
Reset circuit breaker; find out
reason for the trip
|
|
Main power switch is off
|
Turn on main power switch
|
|
Incorrect voltage supply
|
Check voltage; ensure correct
voltage is supplied
|
|
Thermostat setting is too high
|
Lower down thermostat setting
|
|
Thermostat defective/faulty
|
Replace thermostat
|
|
System is in defrost cycle
(freezer)
|
Wait and time defrost cycle
(typical freezer defrost cycle is 30–45 minutes, 2-4 times per day)
|
|
Compressor mechanical and or
electrical problems
|
Check and repair mechanical and
electrical compressor problems
|
|
Power is ON but no display on control board
|
Phase loss
|
Check wiring for breaks
|
Fuse blown
|
Replace fuse
|
|
Power phase open or transformer
shorted
|
Check transformer output
voltage (12 V AC/24 V AC)
|
|
Control board failure
|
Replace control board
|
|
Control board displays but Compressor does not
run
|
Compressor relay tripped
|
Find cause & perform
corrective action
|
Internal thermal overload
tripped
|
Wait until compressor cools
down for reset ( 5 minutes )
|
|
HI-LO pressure safety switch
tripped
|
Determine reason and correct it
before resetting safety switch
|
|
Defective contactor or coil
|
Repair/replace
|
|
Cold Room temperature is lower
than setpoint
|
Reset temperature setpoint
|
|
Compressor malfunction
|
Check compressor motor windings
|
|
Compressor Does Not
Start, No Hum
|
Fuse blown
|
Replace fuse and determine the
reasons why the fuse was blown (shorted/grounded/open/burnt windings,
overloading, etc.)
|
Tripped circuit breaker
|
Reset circuit breaker and find
out the causes why it tripped
|
|
Motor protector open/Thermal
Overload tripped
|
Check motor/overload
protector (overload automatically
resets)
|
|
Improperly wired; Loose wiring
|
Repair/correct the wiring
|
|
Burnt motor windings/open
circuit
|
Check/replace motor winding
|
|
Defective contactor/coil
|
Repair/replace
|
|
Temperature control malfunction
|
Reset/Repair/replace temp.
control
|
|
Pressure control/switch broken
|
Reset/Repair/replace press.
control
|
|
Manual reset button
|
Press manual reset but find out
why button went to reset lockout
|
|
High pressure control lockout
|
Clean dirty condenser coil,
check and repair fan not running, check/repair overcharged refrigerant, then
press Reset
|
|
Lube oil control tripped
|
Check lube oil sight glass,
refrigerant migration, too low/too high oil level, oil leakage, P-trap piping
(oil not returning to compressor), worn oil pump, oil contamination,
crankcase pressurization due to piston blow-by (leakage into the crankcase)
|
|
Compressor Does Not
Start, with Humming Sound
|
Supply voltage too low/too high
|
Check and correct supply
voltage
|
Faulty run or start capacitor
|
Replace run/start capacitor
|
|
Defective start relay
|
Replace start relay
|
|
Compressor improperly wired
|
Correct the wiring
|
|
Shorted/grounded motor windings
|
Repair/replace motor windings
|
|
Un-equalized system pressures
on a PSC motor
|
Off cycle will eventually
equalize system pressures, use hard start kit or bigger start capacitor
|
|
Tight bearings, shaft seized,
broken pistons or rods (mechanical issues)
|
Diagnose and repair/replace
|
|
Compressor Does Not
Start, Hums & Trips on Overload
|
Dirty condenser coil
|
Clean the condenser coil
|
Supply voltage too low/too high
|
Check and correct supply
voltage
|
|
Surrounding area too hot
|
Relocate cabinet or equipment
|
|
Compressor Starts
but Short Cycles
|
Dirty condenser coil
|
Clean the condenser coil
|
Recirculation of discharge air
from condenser
|
Relocate condenser, vent out
discharge air
|
|
Recirculation of discharge air
from evaporator
|
Check for blockage/obstruction
|
|
Discharge pressure high
|
See Discharge Pressure High
|
|
Suction pressure high
|
See Suction Pressure High
|
|
High superheat, Low in
refrigerant
|
Adjust the superheat (rule of
thumb superheat for medium-temperature walk-in cooler is 8° to 10°F;
low-temperature applications is 4° to 6°F)
|
|
Overcharged, undercharged
|
Correct the amount of
refrigerant
|
|
High/Low voltage, voltage
imbalance, voltage out of phase
|
Check and correct the supply
voltage
|
|
High amperage on 3-phase supply
voltage
|
Check mechanical problems
(crankshaft, piston, etc); partially shorted windings
|
|
Low airflow in evaporator
|
Check fan/motor, obstruction
|
|
Low outside air temperature
|
Check low ambient control
|
|
Low humidity, Low load, No
capacity control
|
Check, repair, adjust, install
|
|
Low differential setting on
pressure/temperature control
|
Adjust differential (typical is
15 psig differential on pump down system)
|
|
Low ambient conditions making
un-insulated receiver cold
|
Check/repair/replace insulation
|
|
Liquid line solenoid valve leaking
during off cycle
|
Repair/replace solenoid valve
|
|
Compressor valve leaking
|
Replace compressor valve
|
|
Compressor Starts but
Cycles Off on Overload Protector
|
Suction pressure high
|
See Suction Pressure High
|
Head/discharge pressure high
|
See Discharge Pressure High
|
|
Improper wiring
|
Correct the wiring
|
|
Shorted/grounded motor windings
|
Repair/replace
|
|
Supply voltage low
|
Check and correct the voltage
|
|
Faulty overload protector
|
Replace
|
|
Defective start relay
|
Replace
|
|
Failed start or run capacitor
|
Replace
|
|
Mechanical failure (tight
bearings, seized shaft, broken rods, valves, etc)
|
Repair/replace damaged part/s
|
|
Compressor Pull
High Amps
|
Excessive product load
|
Reduce load
|
Wiring too small
|
Ensure correct gauge sizes of
wiring
|
|
Improperly wired
|
Check and correct the wiring
|
|
Voltage High/Low/Imbalance
|
Check and correct supply
voltage
|
|
Burned relay, contactor
contacts
|
Replace
|
|
Start relay sticks
|
Replace
|
|
Start/Run capacitor
malfunctions
|
Replace
|
|
Mechanical failure (tight
bearings, seized shaft, broken rods, valves, etc)
|
Repair/replace damaged part/s
|
|
Refrigerant wrong (incorrect)
|
Recover and put correct
refrigerant
|
|
Suction pressure high
|
See Suction Pressure High
|
|
Head/discharge pressure high
|
See Discharge Pressure High
|
|
Discharge Pressure
High
|
Dirty condenser coil
|
Clean
|
(normal head pressure for
|
Overcharged
|
Recover and charge proper
amount
|
R404A walk-in cooler: 200-225
psi
|
Fan not running/poor air flow circulation
|
Repair/replace/re-arrange
products
|
R134A: 150-300 psig)
|
Evaporator coil frozen, freeze
up, blocked with ice
|
Check/allow defrost; check
thermostat setting not too cold; check gasket seals
|
Estimate Hi-Side pressure =
Ambient temp (F) x 2.2
|
Thermostat set too high
|
Set thermostat to lower
temperature
|
Cabinet door is open/not
sealing
|
Close door/check or replace
door seals
|
|
Excessive product/load inside
cabinet
|
Decrease load/allow time to
cool down
|
|
Exterior thermometer out of
calibration
|
Calibrate/replace thermometer
|
|
(Air-cooled system)
|
Condenser outlet air
recirculation
|
Check condenser air outlet
location
|
Insufficient clearance around
cabinet
|
Ensure adequate air space/flow
|
|
Condenser air flow restriction
|
Ensure unobstructed air flow
|
|
Ambient temperature too warm
|
Relocate away from heat
generating equipment (oven, stove, dryer, etc.)
|
|
Discharge line restriction
|
Fix restriction
|
|
Incorrect fan motor or fan
blade
|
Fix/replace with correct parts
|
|
Air and/or non-condensable
gases in the system
|
Remove air and non-condensable
gases in the system; check for leaks
|
|
(Water-cooled system)
|
Restricted/Incorrect water flow
|
Check/repair water flow
|
Cooling water too warm
|
Check water temperature
|
|
Condenser tubes restricted
|
Clean condenser tubes
|
|
Defective water regulating
valve
|
Replace water regulating valve
|
|
Discharge Pressure Low
|
Low/insufficient refrigerant
|
Check for leaks, repair, add
charge
|
Low suction pressure
|
See Suction Pressure Low
|
|
Ambient air too cold
|
Check/Install low ambient control
|
|
Damaged compressor valves/rods
|
Repair/replace
|
|
Uninsulated receiver acting as
condenser
|
Insulate
|
|
Water too cold/defective water
regulating valve (water-cooled)
|
Repair/replace
|
|
Suction Pressure Low
|
Low/lack of refrigerant
|
Check for leaks, repair, add
charge
|
Dirty Evaporator
|
Clean evaporator
|
|
Iced/frozen evaporator
|
Repair, defrost
|
|
Fan motor/fan blade (air flow)
defective
|
Repair/replace
|
|
Expansion valve underfeeding
|
Adjust/regulate Superheat
setting
|
|
Plugged suction filter
|
Replace suction filter
|
|
Suction Pressure
High
|
Excessive load
|
Reduce load
|
(normal suction pressure for R404A
walkin cooler is 55-60 psig;
|
Metering device overfeeding
|
Adjust TXV Superheat setting
|
R134A: 30-40 psig)
|
Metering device Superheat set
too low
|
Adjust TXV Superheat setting
|
Compressor discharge valve leak
|
Repair leak
|
|
Hot gas bypass valve leak
|
Repair leak
|
|
Hot gas defrost solenoid leak
|
Repair leak
|
|
Defective or incorrect metering
device installed
|
Replace metering device
|
|
Oversized metering device
|
Replace metering device
|
|
Metering device held open by
foreign material causing liquid flood back
|
Repair/replace
|
|
Metering device frozen in open
position due to moisture in the system
|
Repair, evacuate, recharge
|
|
External equalizer on metering
device is plugged or capped
|
Clean/repair/replace
|
|
Ruptured suction line to the
liquid line heat exchanger
|
Repair the rupture
|
|
Unit has just completed Defrost
Mode and has just started Cooling Mode
|
This is normal, wait and
monitor
|
|
High-Temperature Alarm
|
Product Overload
|
Reduce product load
|
Excessive door opening
|
Reduce door opening
|
|
Poor refrigeration
efficiency/performance
|
See Suction Pressure High
See Discharge Pressure High
|
|
Frost build-up on Evaporator
|
See Frost on Evaporator fins
|
|
Frost on Evaporator fins
|
Incomplete defrost cycle
|
Defrost manually, adjust
defrost setting
|
[normal setting: 4 times a day, 30 minutes defrost (off) cycle]
|
Defrost time intervals too long
|
Adjust defrost time and
interval setting ( 4 x 30 )
|
Coil frosted during defrost
|
Heater malfunction
|
Check/repair/replace
|
Insufficient defrost cycles per
day
|
Adjust defrost control settings
|
|
Ice build up on Drain Pan
|
Defective heater
|
Check/repair/replace
|
Drain line plugged
|
Clean
|
|
Large Temperature Difference between actual
cold storage box & control panel setpoint
|
Incorrect room temperature
|
Re-position sensing point of
temperature sensor
|
Sensor placement, wire too long
|
Check placement, enlarge wire
section
|
|
Sensor contactor open
|
Reconnect sensor
|
|
Walk-in Cooler, Refrigerator, or Freezer runs
too long/continuously
|
Too much warm product is loaded
on Cabinet/Cold Room Storage
|
Allow adequate time for product
to cool down
|
Door is open
|
Close door
|
|
Excessive door opening
|
Avoid prolonged door openings
|
|
Door gasket not sealing
properly
|
Adjust door/Replace gasket
|
|
No product inside the cabinet
|
Load cabinet with products
|
|
Dirty condenser coil
|
Clean
|
|
Airflow problems around
condensing unit
|
Provide good air space; Relocate
away from heat, hot equipment, sunlight
|
|
Frozen/iced evaporator
|
Defrost coil, ensure door
gasket is sealed and thermostat not set too cold
|
|
Cabinet is Noisy
|
Loose parts
|
Tighten
|
Vibration of tubing
|
Ensure no contact of tubing
with other components
|
|
Refrigerator is freezing products
|
Cabinet is overloaded with
products
|
Decrease load and re-arrange
products
|
Thermostat set too low
|
Set thermostat to higher
setting
|
|
Condensation on Cabinet face
|
Face heaters are turned OFF
|
Turn ON
|
Digital Thermometer blank, flashing, incorrect
temperature, odd characters
|
System not running/temperature
too high
|
See System Not Running, Discharge
Pressure High, High Temperature Alarm
|
Thermometer probe wire
disconnected
|
Reconnect probe wire
|
|
Incorrect power to thermometer
|
Check Transformer, Battery
|
|
Display module out of
calibration
|
Calibrate using procedure on
Manual
|
|
Run Capacitor burned out
|
Supply voltage excessively high
|
Check/Repair/Replace
|
Incorrect capacitor
|
Replace with correct
specification
|
|
Capacitor voltage rating too
low
|
Replace with higher voltage
rating
|
|
Start Capacitor burned out
|
Compressor is short cycling
|
Repair
|
Relay contacts sticking
|
Replace
|
|
Incorrect capacitor
|
Replace with correct one
|
|
Start winding staying in
circuit too long
|
Repair/replace
|
|
Start Relay contacts stick
|
Compressor runs in short time
duration
|
Repair/Adjust
|
No bleed resistor on the start
capacitor
|
Replace with Start Capacitor
having a bleed resistor
|
|
Start Relay burned out
|
Compressor short cycling
|
Repair/Check
|
Supply voltage high or low
|
Adjust/Repair
|
|
Relay improperly mounted
|
Ensure arrow is UP on the side
of relay
|
|
Start or Run Capacitor is
incorrect
|
Replace with correct capacitors
|
|
Starting Relay is incorrect
|
Replace with correct relay specifications
with the compressor manufacturer
|
|
- http://www.hvacrinfo.com/trouble.htm