Shop at Amazon.ca

Wednesday, September 13, 2017

Refrigeration, Air Conditioning Troubleshooting Flowchart Guide



REFRIGERATION TROUBLESHOOTING FLOWCHART
There are 7 Steps of a Systematic Refrigeration Troubleshooting Flowchart.
          1. Determine Problem
          2. Look for Signs/Symptoms
          3. Determine Causes of Problem
          4. Perform Logical Elimination Process
          5. Find the Most Probable Cause
          6. Correct the Defect
          7. Recheck System Operation


          

MOST COMMON REFRIGERATION PROBLEMS
1. Undercharge/Leak
2. Frozen/Iced Evaporator
3. Overcharge
4. Restriction
5. High Discharge Temperature/High Head Pressure
6. Compressor Problems
7. Fan/Motor Problems
8. Electrical Components Problems  
  




Example I:  REFRIGERATION TROUBLESHOOTING FLOWCHART

1. Determine Problem:  POOR COOLING

2. Signs/Symptoms:
·        presence of oil leaks
·        rapid compressor cycling (orifice tube systems)
·        bubbles/foam on sight glass
·        low side/suction pressure Low
·        high side/discharge/head pressure Low

3. Possible Causes of Problem:
·        undercharged – insufficient refrigerant charge (foam/bubbles in sight glass)
·        leak
·        plugged suction filter
·        ice build up on evaporator
·        dirty evaporator
·        restriction in evaporator
·        faulty/defective fan
·        metering device (expansion valve) underfeeding


4. Perform Logical Elimination Process
     - narrow down the causes of the problem in logical systematic fashion

5. Find Most Probable Cause
     - using tools to conduct functional tests and performance tests to find out
       the most likely root cause of the problem
     - example: most probable cause is undercharge due to a leak

6. Correct the Defect
     - repair the leak and add appropriate amount of refrigerant

7. Recheck System Operation
    - conduct another performance test and check temperatures and pressures
      to ensure system is back to correct normal operation








Example 2:  NO COOLING – UNDERCHARGED/LOW REFRIGERANT/LEAK

Actual Repairman/Serviceman procedure: R22 system
1. Customer complaint report – NO COOLING
2. Look at the Thermostat, ensure it is in COOL mode and set at 70 F
3. Feel the supply duct whether it is blowing hot air
4. Check the return air filter
5. Determine which loads are running: Indoor Fan, Outdoor Fan, Compressor
6. Measure amperage of compressor using Multi-tester clamp-on meter (for Residential AC: normal compressor amps = 11 A)
7. By the process of elimination, since all 3 loads are running, therefore the problem is mechanical
8. Check for debris around condensing unit (leaves, grass, etc.)
9. Calculate Superheat:
     a.  Measure indoor wet bulb temperature – place psychrometer in return air duct (psychrometer reading:  70 F)
     b. Measure outdoor dry bulb temperature – place psychrometer near condensing unit (measurement reading: 95 F)
     c. Measure suction line pressure using manifold gage (reading: 50 psig)
     d. Use PT CHART to determine evaporation temperature corresponding to 50 psig --- 26 F
    
  
     e. Determine actual temperature of suction line using Multimeter Probe:  75 F
     f. Calculate Superheat = Actual suction line temp – evaporation temp at 50 psig
         Superheat = 75 – 26 = 49 F
     g. Using SUPERHEAT CHART corresponding to 95 F dry bulb and 70 F wet bulb temperatures, the superheat is 18 F

 
10. Using Mechanical Air Conditioning Fault Table, determine what the problem is: Leak/Undercharged

11. Check for leaks on the indoor & outdoor units using soap and bubble or electronic leak detector

12. Add refrigerant



---------------------------------------------------------------------------------------------------




Determine Problem:  INADEQUATE COOLING
Signs/Symptoms:
- suction pressure is high
- head pressure is high
- continuous compressor operation (orifice tube systems)
- ice or frost on condenser
- ice on evaporator coil

Possible Causes:
- overcharged – too much refrigerant charge
- evaporator freeze up/iced up
- thermostat temperature setting too high
- dirty condenser coil
- restriction in condenser coil
- fan not running
- fan blade reversed
- poor air circulation
- excessive load/warm products
- door open/door seal broken
- thermostatic expansion valve (TXV/TEV) overfeeding
- insufficient clearance around cabinet
- high ambient temperature



Determine Problem:  RESTRICTION
Signs/Symptoms:
- no cooling/poor cooling
- gauge pressures lower than normal
- compressor cycles frequently
- frost on high pressure lines
- suction pressure is from low to vacuum
- head pressure is low

Possible Causes:
- defective compressor
- contaminants such as dirt or corrosion
- defective TXV/TEV
- plugged orifice
- plugged/defective filter-drier







------------  OTHER  REFRIGERATION  PROBLEMS  ------------

Compressor Not Running, Correct Voltage & Phase:
1. Check voltage within 10%
2. Check Overload Protector
3. Check Start Capacitor
4. Check Start Relay
5. Check Amp Draw of compressor.  If very low compared to RLA/FLA, check:
       _ broken discharge valves
       _ broken suction valves
       _ broken crank
       _ broken push rod


Compressor Not Running, Incorrect Voltage & Phase:
1. Test circuit for voltage loss & phase loss
2. Test contactor
3. Check control relay
4. Check safety devices such as High Pressure Switch, Low Pressure Switch, Oil Pressure Safety Switch.
5. Before pressing Reset on the safety devices, find out reason why it tripped and fix it.


High Head Pressure on Water-cooled Condenser:
1. Check High Pressure Control. If tripped, adjust setting on water regulating valve to achieve manufacturer's recommended pressure.
2. Check water flow. If insufficient:
           - check water supply and plumbing
           - check water inlet temperature
           - check water outlet temperature, if high, adjust water regulating valve to recommended pressure
            - check condition of valve, if defective, worn or scaled with calcium/mineral deposit, replace valve
3. If water flow is sufficient:
            - reset high pressure control if tripped
            - determine temperature differential (TD) between condenser water outlet & inlet
            - if TD is too low, condenser is dirty or has calcium/mineral build-up
            - acid solution can be circulated into condenser to remove mineral deposits and improve heat transfer according to manufacturer's instructions/procedure


High Head Pressure on Air-cooled Condenser:
1. Check if condenser is dirty, clean coil using wash down or high pressure system
2. Check condenser fan motor correct rotation
3. Check for worn, loose or broken belt
4. Check fan blade condition, size, and correct direction (not installed backwards)
5. Check motor bearing, if there is side to side play, replace motor
6. If condenser is facing south, move north or install shade
7. If ambient temperature is high or condenser is located near heat-producing equipment, relocate and find solution to prevent overheating 



                                         --------------------------------------------------------------------------------------


NORMAL CONDITIONS FOR R134A SYSTEM:
Ambient temp:  80 F --- 27 C
Humidity:  50% RH
Air outlet temp of supply:  12 C --- 53 F
Lo-Side:  40 psig
Hi-Side:  320 psig
Sight glass:  clear --- adequate refrigerant
                      (foamy --- insufficient refrigerant
                        frosty --- almost nothing
                        no foam --- too much)










Air Conditioning Diagnostic Charging Table:
 
Compressor and Electric Components Troubleshooting:

Refrigeration Troubleshooting: Causes and Remedy

AC/Furnace Troubleshooting:

Heat Pump Troubleshooting Guide:

Sample Refrigeration Troubleshooting Flowchart:
                                                                                



Table 1.  HOW TO TROUBLESHOOT COMMON REFRIGERATION PROBLEMS:
PROBLEM
POSSIBLE CAUSES
SOLUTION/REMEDY
System Not Running
Power cord not plugged in
Plug in power cord

Fuse blown
Replace fuse; find out reason blown

Circuit breaker tripped
Reset circuit breaker; find out reason for the trip

Main power switch is off
Turn on main power switch

Incorrect voltage supply
Check voltage; ensure correct voltage is supplied

Thermostat setting is too high
Lower down thermostat setting

Thermostat defective/faulty
Replace thermostat

System is in defrost cycle (freezer)
Wait and time defrost cycle (typical freezer defrost cycle is 30–45 minutes, 2-4 times per day)

Compressor mechanical and or electrical problems
Check and repair mechanical and electrical compressor problems



Power is ON but no display on control board
Phase loss
Check wiring for breaks

Fuse blown
Replace fuse

Power phase open or transformer shorted
Check transformer output voltage (12 V AC/24 V AC)

Control board failure
Replace control board



Control board displays but Compressor does not run
Compressor relay tripped
Find cause & perform corrective action

Internal thermal overload tripped
Wait until compressor cools down for reset  ( 5 minutes )

HI-LO pressure safety switch tripped
Determine reason and correct it before resetting safety switch

Defective contactor or coil
Repair/replace

Cold Room temperature is lower than setpoint
Reset temperature setpoint

Compressor malfunction
Check compressor motor windings



Compressor Does Not Start, No Hum
Fuse blown
Replace fuse and determine the reasons why the fuse was blown (shorted/grounded/open/burnt windings, overloading, etc.)

Tripped circuit breaker
Reset circuit breaker and find out the causes why it tripped

Motor protector open/Thermal Overload tripped
Check motor/overload protector  (overload automatically resets)

Improperly wired; Loose wiring
Repair/correct the wiring

Burnt motor windings/open circuit
Check/replace motor winding

Defective contactor/coil
Repair/replace

Temperature control malfunction
Reset/Repair/replace temp. control

Pressure control/switch broken
Reset/Repair/replace press. control

Manual reset button
Press manual reset but find out why button went to reset lockout

High pressure control lockout
Clean dirty condenser coil, check and repair fan not running, check/repair overcharged refrigerant, then press Reset

Lube oil control tripped
Check lube oil sight glass, refrigerant migration, too low/too high oil level, oil leakage, P-trap piping (oil not returning to compressor), worn oil pump, oil contamination, crankcase pressurization due to piston blow-by (leakage into the crankcase)



Compressor Does Not Start, with Humming Sound
Supply voltage too low/too high
Check and correct supply voltage

Faulty run or start capacitor
Replace run/start capacitor

Defective start relay
Replace start relay

Compressor improperly wired
Correct the wiring

Shorted/grounded motor windings
Repair/replace motor windings

Un-equalized system pressures on a PSC motor
Off cycle will eventually equalize system pressures, use hard start kit or bigger start capacitor

Tight bearings, shaft seized, broken pistons or rods (mechanical issues)
Diagnose and repair/replace



Compressor Does Not Start, Hums & Trips on Overload
Dirty condenser coil
Clean the condenser coil

Supply voltage too low/too high
Check and correct supply voltage

Surrounding area too hot
Relocate cabinet or equipment



Compressor Starts but Short Cycles
Dirty condenser coil
Clean the condenser coil

Recirculation of discharge air from condenser
Relocate condenser, vent out discharge air

Recirculation of discharge air from evaporator
Check for blockage/obstruction

Discharge pressure high
See Discharge Pressure High

Suction pressure high
See Suction Pressure High

High superheat, Low in refrigerant
Adjust the superheat (rule of thumb superheat for medium-temperature walk-in cooler is 8° to 10°F; low-temperature applications is 4° to 6°F)

Overcharged, undercharged
Correct the amount of refrigerant

High/Low voltage, voltage imbalance, voltage out of phase
Check and correct the supply voltage

High amperage on 3-phase supply voltage
Check mechanical problems (crankshaft, piston, etc); partially shorted windings

Low airflow in evaporator
Check fan/motor, obstruction

Low outside air temperature
Check low ambient control

Low humidity, Low load, No capacity control
Check, repair, adjust, install

Low differential setting on pressure/temperature control
Adjust differential (typical is 15 psig differential on pump down system)

Low ambient conditions making un-insulated receiver cold
Check/repair/replace insulation

Liquid line solenoid valve leaking during off cycle
Repair/replace solenoid valve

Compressor valve leaking
Replace compressor valve



Compressor Starts but Cycles Off on Overload Protector
Suction pressure high
See Suction Pressure High

Head/discharge pressure high
See Discharge Pressure High

Improper wiring
Correct the wiring

Shorted/grounded motor windings
Repair/replace

Supply voltage low
Check and correct the voltage

Faulty overload protector
Replace

Defective start relay
Replace

Failed start or run capacitor
Replace

Mechanical failure (tight bearings, seized shaft, broken rods, valves, etc)
Repair/replace damaged part/s



Compressor Pull High Amps
Excessive product load
Reduce load

Wiring too small
Ensure correct gauge sizes of wiring

Improperly wired
Check and correct the wiring

Voltage High/Low/Imbalance
Check and correct supply voltage

Burned relay, contactor contacts
Replace

Start relay sticks
Replace

Start/Run capacitor malfunctions
Replace

Mechanical failure (tight bearings, seized shaft, broken rods, valves, etc)
Repair/replace damaged part/s

Refrigerant wrong (incorrect)
Recover and put correct refrigerant

Suction pressure high
See Suction Pressure High

Head/discharge pressure high
See Discharge Pressure High



Discharge Pressure High
Dirty condenser coil
Clean
(normal head pressure for
Overcharged
Recover and charge proper amount
R404A walk-in cooler: 200-225 psi
Fan not running/poor air flow circulation
Repair/replace/re-arrange products
R134A: 150-300 psig)
Evaporator coil frozen, freeze up, blocked with ice
Check/allow defrost; check thermostat setting not too cold; check gasket seals
Estimate Hi-Side pressure = Ambient temp (F)  x  2.2
Thermostat set too high
Set thermostat to lower temperature

Cabinet door is open/not sealing
Close door/check or replace door seals

Excessive product/load inside cabinet
Decrease load/allow time to cool down

Exterior thermometer out of calibration
Calibrate/replace thermometer
(Air-cooled system)
Condenser outlet air recirculation
Check condenser air outlet location

Insufficient clearance around cabinet
Ensure adequate air space/flow

Condenser air flow restriction
Ensure unobstructed air flow

Ambient temperature too warm
Relocate away from heat generating equipment (oven, stove, dryer, etc.)

Discharge line restriction
Fix restriction

Incorrect fan motor or fan blade
Fix/replace with correct parts

Air and/or non-condensable gases in the system
Remove air and non-condensable gases in the system; check for leaks
(Water-cooled system)
Restricted/Incorrect water flow
Check/repair water flow

Cooling water too warm
Check water temperature

Condenser tubes restricted
Clean condenser tubes

Defective water regulating valve
Replace water regulating valve



Discharge Pressure Low
Low/insufficient refrigerant
Check for leaks, repair, add charge

Low suction pressure
See Suction Pressure Low

Ambient air too cold
Check/Install low ambient control

Damaged compressor valves/rods
Repair/replace

Uninsulated receiver acting as condenser
Insulate

Water too cold/defective water regulating valve (water-cooled)
Repair/replace



Suction Pressure Low
Low/lack of refrigerant
Check for leaks, repair, add charge

Dirty Evaporator
Clean evaporator

Iced/frozen evaporator
Repair, defrost

Fan motor/fan blade (air flow) defective
Repair/replace

Expansion valve underfeeding
Adjust/regulate Superheat setting

Plugged suction filter
Replace suction filter



Suction Pressure High
Excessive load
Reduce load
(normal suction pressure for R404A walkin cooler is 55-60 psig;
Metering device overfeeding
Adjust TXV Superheat setting
R134A: 30-40 psig)
Metering device Superheat set too low
Adjust TXV Superheat setting

Compressor discharge valve leak
Repair leak

Hot gas bypass valve leak
Repair leak

Hot gas defrost solenoid leak
Repair leak

Defective or incorrect metering device installed
Replace metering device

Oversized metering device
Replace metering device

Metering device held open by foreign material causing liquid flood back
Repair/replace

Metering device frozen in open position due to moisture in the system
Repair, evacuate, recharge

External equalizer on metering device is plugged or capped
Clean/repair/replace

Ruptured suction line to the liquid line heat exchanger
Repair the rupture

Unit has just completed Defrost Mode and has just started Cooling Mode
This is normal, wait and monitor



High-Temperature Alarm
Product Overload
Reduce product load

Excessive door opening
Reduce door opening

Poor refrigeration efficiency/performance
See Suction Pressure High
See Discharge Pressure High

Frost build-up on Evaporator
See Frost on Evaporator fins



Frost on Evaporator fins
Incomplete defrost cycle
Defrost manually, adjust defrost setting
[normal setting:  4 times a day,  30 minutes defrost (off) cycle]
Defrost time intervals too long
Adjust defrost time and interval setting ( 4 x 30 )



Coil frosted during defrost
Heater malfunction
Check/repair/replace

Insufficient defrost cycles per day
Adjust defrost control settings



Ice build up on Drain Pan
Defective heater
Check/repair/replace

Drain line plugged
Clean



Large Temperature Difference between actual cold storage box & control panel setpoint
Incorrect room temperature
Re-position sensing point of temperature sensor

Sensor placement, wire too long
Check placement, enlarge wire section

Sensor contactor open
Reconnect sensor






Walk-in Cooler, Refrigerator, or Freezer runs too long/continuously
Too much warm product is loaded on Cabinet/Cold Room Storage
Allow adequate time for product to cool down

Door is open
Close door

Excessive door opening
Avoid prolonged door openings

Door gasket not sealing properly
Adjust door/Replace gasket

No product inside the cabinet
Load cabinet with products

Dirty condenser coil
Clean

Airflow problems around condensing unit
Provide good air space; Relocate away from heat, hot equipment, sunlight

Frozen/iced evaporator
Defrost coil, ensure door gasket is sealed and thermostat not set too cold



Cabinet is Noisy
Loose parts
Tighten

Vibration of tubing
Ensure no contact of tubing with other components



Refrigerator is freezing products
Cabinet is overloaded with products
Decrease load and re-arrange products

Thermostat set too low
Set thermostat to higher setting



Condensation on Cabinet face
Face heaters are turned OFF
Turn ON



Digital Thermometer blank, flashing, incorrect temperature, odd characters
System not running/temperature too high
See System Not Running, Discharge Pressure High, High Temperature Alarm

Thermometer probe wire disconnected
Reconnect probe wire

Incorrect power to thermometer
Check Transformer, Battery

Display module out of calibration
Calibrate using procedure on Manual






Run Capacitor burned out
Supply voltage excessively high
Check/Repair/Replace

Incorrect capacitor
Replace with correct specification

Capacitor voltage rating too low
Replace with higher voltage rating



Start Capacitor burned out
Compressor is short cycling
Repair

Relay contacts sticking
Replace

Incorrect capacitor
Replace with correct one

Start winding staying in circuit too long
Repair/replace



Start Relay contacts stick
Compressor runs in short time duration
Repair/Adjust

No bleed resistor on the start capacitor
Replace with Start Capacitor having a bleed resistor



Start Relay burned out
Compressor short cycling
Repair/Check

Supply voltage high or low
Adjust/Repair

Relay improperly mounted
Ensure arrow is UP on the side of relay

Start or Run Capacitor is incorrect
Replace with correct capacitors

Starting Relay is incorrect
Replace with correct relay specifications with the compressor manufacturer



















Credits/References:
- youtube
- delmar cengage
- trutechtools.com/testo
- lg ac mechanical troubleshooting guide
- http://www.hvacrinfo.com/trouble.htm