PROBLEM:


An air-conditioning system draws 10% outdoor air at a dry bulb temperature of 42 C / 108 F. If the return air is at 28 C / 82 F, determine the dry bulb temperature of the mixed air.



Given

10% outdoor air


42C/108F outdoor air temperature 


28C/82F return air temperature 



Unknown 

dry bulb temperature of mixed air



SOLUTION:


(% Outdoor Air  x  Temperature)  +  

(% Indoor Return Air  x Temperature)  = 100%  x  Air Mixture Temperature


using Celcius temperatures and substituting given values, we have


( 10% x 42 )  +  

( 90% x 28 ) = 100% x Air Mixture Temp


Mixed air temp 

= 4.2 + 25.2 

= 29.4 C / 85 F